Sewage Treatment Conversion Units

The MANTAIR range of sewage treatment conversion units provide a discrete, reliable and cost effective solution to sewage treatment for domestic dwellings and small scale commercial and industrial premises without mains drainage, but where an existing septic tank or cesspool is present.

Supplied to site as a purpose made singe unit, the MANTAIR unit fits into the existing septic tank or cesspool, effectively converting it into a small sewage treatment plant and no further filters or soakaway’s are therefore necessary.

The long established principle of aerobic purificationis at the heart of the Mantair™  system. Aeration of waste sewage encourages the growth of aerobic bacteria which degrades the sewage. The effluent produced complies with the requirements of the Enviroment Agency, for England and Wales, and Scottish Environment Protection Agency for discharge direct to a natural watercourse.

  • Complies with BS 6297 : 1983
  • Effluent to Environment Agency standard.


Benefits
  • It's the most economically installed treatment system in the UK;
  •  Does not require the installation of any tankage, thus avoiding the disturbance of established gardens;           
  • The treatment plant is completely hidden from view;
  • Designed to produce an effluent in compliance with the Regulating Authorities;
  • Peace of mind with a lifetime Process Guarantee;
  • The efficient air blower is both quiet and economical with low running costs;
  • Integral surge control system;
  • Works in high water table areas; 
  • It requires less than two hours maintenance per year;
  Unique Design

The MANTAIR™  Conversion unit is the only sewage treatment unit in the UK which converts existing tanks into sewage treatment plants. Each Mantair™  Conversion unit is purpose-built to suit the depth, diameter, invert depth and access shaft of the existing tank.

How Does It Work?

The Mantair™ Conversion Unit is powered by a small air blower, which can be located in either an existing outbuilding or in a 'Beehive' – a purpose built blower housing designed to blend into the natural setting.

The blower can be located up to 25 metres from the MANTAIR™ Conversion Unit and is powered by domestic 240v electrical supply. It is a connected to the unit by a small bore MDPE pipe concealed underground. The blower provides the air that is required for the treatment process and to lift the treated effluent to the discharge point.

Installation & Commissioning

  The first stage is to carry out an initial survey of your existing tank. This enables us to determine the condition of the tank and to ascertain the dimensions required by MANTAIR™ to manufacture your unit. Each conversion unit is custom built.

  The second stage is the on – site installation. The MANTAIR™ unit when installed stands on the floor of the existing tank. The tank must therefore be emptied and all debris removed from the floor of the tank prior to the installation taking place.

  On the majority of sites only minor civil engineering works need to be carried out. This minimises the disturbance to established gardens.  Finally the unit is commissioned by our operatives, to ensure optimum operational effectiveness, of your MANTAIR™unit

Maintenance

The Mantair™ Conversion Unit is simpler to maintain then most other treatment plants as there are not electrical, mechanical or moving parts within the underground treatment zone.

Technical information on the MANTAIR range of sewage treatment conversion units is available at

www.mantair.com.

Mantair™ Conversion Units are proffessionally installed by one of our Licencesed Contractors;

 Mantair™ Units are not available through wholesale or retail outlets;

All Licencensed Contrators offer a comprehensive service. This includes an initial site survey, guidance and advice on system selection., complete installation and commissioning of your treatment plant and full after sales sevice.                                    

                                                                                                                                      

Mantair



  


Number
 of Persons
Maximum
 Flow
Litres/Day

B.O.D Load
Kg/Day
Air Blower
Rating
Kg/Day
5
1000
0.275
0.086
7
1400
0.385
0.086
10
2000
0.550
0.100
12
2400
0.660
0.130
15
3000
0.825
0.130